  PVC insulated 3-4 core sheathed flat cables for internal wiring
   
  Cable Structure     Technical Data
  Generally conforms to, CENELEC HD 21, UL-83, IEC 60227, BS   6500, DIN VDE 0281, IS 694  
     
 
Operating tem.: -20°c to max.+80°C
Nominal voltage: 1100 V
Test voltage: 3000 V
Min. bending radius: 6 x cable diameter
Flame propagation: Flame retardant test as per IEC 60332-1
 
     
   
  Copper:  
  EC flexible copper Generally conforms to IEC 60228, DIN VDE   0295,IS 8131  
   
  Insulation:  
   PVC insulation compound TI-1  
   
  Outer Sheath:  
   Speacial PVC : Black, Blue  
   
   *Any other Color on specific request can also be supplied  
     
  Cable Features     Application
     
   Good insulation properties when submerged in winter  
  PVC Flat - 3 & 4 Core
  Jainson submersible pump cables are used as supply and control cables for engines for submersible pumps, underwater lighting, and floating switches etc. up to the depth of 500 m and water temperature up to +75°C. These cables are ideal for outer installations in dry, moist and wet environments but however not suitable for explosive areas.
   
  Standard length cable packing:
  Coils 100, 200,300 and 500, 1000m. in wooden reels
   
   Quality backed by 40 years experience in cable industry
   Excellent resistant to moisture, abrasion, grace, oil
   Longer Flex Life
   Excellent mechanical & electrical properties
   Generally Conforming to : CENELEC HD 21, IEC 60227, UL-83,       BS 6500, DIN VDE 0281, IS 694
   Approved by GWSSB, GWRDC, TWAD, PHED, PSTC, ONGC,       Railways, Mines etc
   Tested by SGS, EIL, RITES, NPC
 
  Cable Design
     
    A submersible Pump cable is a specialized product to be used for submersible pumps in a deep well. The area of installation is         physically  restrictive, and the environment is very hostile. Jainson is designed and manufactured keeping in mind these factors to     achieve the highest possible degree of reliability.
 
Cores colour: Core Identification
Color coding As per IEC 60227 As per IS 694
3 Core Black, Light Blue and Brown Red, Yellow and Blue
4 Core Black, Light Blue, Brown, Yellow with Green Line/ Green with Yellow Line Red , Yellow, Blue, Green / Black
 
 
 
  Technical DataTable    
 
PVC Flat - 3 core
Conductor PVC Insulation PVC Sheath Conductor Resistance at 20°C (max) Current Rating at 40°C
Nominal Area in Nos. & Dia. of wire Nominal Thickness Nominal Core Dia. Nominal Thickness Approx. Overall Dimensions
Thickness Width
Sq. mm. Nos./mm mm mm mm mm mm Ω/km Amps.
1.5 22/0.30 0.8 3.25 1.15 6 12.8 12.1 14
2.5 36/0.30 0.9 3.84 1.15 6.4 14.6 7.41 18
4 56/0.30 1 4.5 1.15 7.4 16.8 4.95 26
6 84/0.30 1 5.3 1.15 7.9 18.7 3.30 31
10 140/0.30 1 6.5 1.4 9.9 23.7 1.91 42
16  224/0.30 1 8 1.4 11.4 28 1.21 57
25 350/0.30 1.2 10.1 2 14.7 35.5 0.780 72
35 490/0.30 1.2 11.3 2 16.2 39.5 0.554 90
50 703/0.30 1.4 13.6 2.2 18.3 45.5 0.386 115
70 988/0.30 1.4 15.3 2.2 20 51 0.272 143
95 1349/0.30 1.6 18 2.4 23.5 60 0.206 165
 
 
  • The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360
  • In view of continuous improvements in our design and process, specifications given here in are subject change without notice.
 
PVC Flat - 4 core
Conductor PVC Insulation PVC Sheath Conductor Resistance at 20°C (max) Current Rating at 40°C
Nominal Area in Nos. & Dia. of wire Nominal Thickness Nominal Core Dia. Nominal Thickness Approx. Overall Dimensions
Thickness Width
Sq. mm. Nos./mm mm mm mm mm mm Ω/km Amps.
1.5 22/0.30 0.8 3.25 1.3 6 15.8 12.1 14
2.5 36/0.30 0.9 3.84 1.3 6.5 18 7.41 18
4 56/0.30 1 4.5 1.45 7.6 21 4.95 26
6 84/0.30 1 5.3 1.5 7.9 24.3 3.30 31
10 140/0.30 1 6.5 1.8 9.9 29.7 1.91 42
16  224/0.30 1 8 1.95 11.8 36 1.21 57
25 350/0.30 1.2 10.1 2 14.7 45.1 0.780 72
35 490/0.30 1.2 11.5 2 16.2 50.1 0.554 90
50 703/0.30 1.4 13.6 2.2 18.3 58.1 0.386 115
70 988/0.30 1.4 15.3 2.2 20 66.5 0.272 143
95 1349/0.30 1.6 18 2.4 23.5 77.3 0.206 165
 
 
 
  • The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360
  • In view of continuous improvements in our design and process, specifications given here in are subject change without notice.
 
PVC Flat - 3 core as per IS 694 : 1990 with ISI mark
Conductor PVC Insulation PVC Sheath Current Rating at 40°C
Nominal Area in Nos. & Dia. of wire Nominal Thickness Nominal Thickness Approx. Overall Dimensions
Thickness Width
Sq. mm. Nos./mm mm mm mm mm Amps.
1.5 22/0.30 0.6 0.9 5.2 11.3 14
2.5 36/0.30 0.7 1 6.2 13.3 18
4 56/0.30 0.8 1 7 15.6 26
6 84/0.30 0.8 1.1 7.4 17.7 31
 
 
 
  • The number of wires is approximate and wire diameter is nominal.
  • They shall be so as to satisfy the requirements of conductor resistance as per
    • The number of wires is approximate and wire diameter is nominal.
    • They shall be so as to satisfy the requirements of conductor resistance as per
 
 
  Submersible pump cables
  +   PVC 3 Core Flat Cables
  +   PVC 4 Core Flat Cables
  +   PVC 3 Core Round Cables
  +   PVC 4 Core Round Cables
  +   Rubber 3 Core Flat Cables
  +   Rubber 4 Core Flat Cables
  +   Rubber 3 Core Round  Cables
  +   Rubber 4 Core Round Cables
  +   DRINCABLE
  +   H07RN-F CABLES
  AWG Pump Cables  |
  Flexible Cables  |
  Welding cables  |
 
All Rights Reserve Jainson Cables India Pvt. Ltd. Maintained by : Macro World Softwares